Wikipedia

Search results

Monday, August 20, 2018

HVAC requalification












REQUALIFICATION
PROTOCOL OF HVAC SYSTEM
                                                         BUILDING - X, XXX FACILITY





















1.0     OBJECTIVE:

The objective of this protocol is to provide procedure for the Requalification of the HVAC system of Building–‘X’ XXX-Facility and to provide the documented evidence that the system is capable to continuously supply the clean and conditioned air with the specified quality attributes thereby establishing its dependability.
Implementation of new ISO-14644-1, 2nd edition 2015. Refer change control no.: XXXXX

2.0     SCOPE:

This protocol covers all aspects of Requalification for the HVAC system (AHU, LAF, Tunnel, Pass Box and Garment Cubicles), which are located in Building–‘X’, XXX-facility .

3.0     ResponsiB1litIEs:

Qualification team comprising the representatives from the following departments shall be responsible for execution of the plan as per this protocol.
DEPARTMENT
RESPONSIBILITY






Sterility assurance services














Sterility assurance services
Executive (Junior/Senior):
·        Shall prepare the requalification protocol/report as per cGMP requirement and organization’s quality norms.
·        Shall ensure that the raw data is complying with the acceptance criteria as mentioned in the protocol.
·        Shall report any abnormality and take corrective and preventive action in coordination with respective department head.
Asst. Manager/Deputy Manager:
·        Shall review the protocol and report.
·        Shall ensure that the raw data is complying with the acceptance criteria as mentioned in the protocol.
HOD/Designee:
·        Shall review and approve the protocol and report.
·        Shall ensure that the raw data is complying with the acceptance criteria as mentioned in the protocol.
Operator/Executor:
·        Shall ensure and follow the procedure as written in the protocol.
·        Shall ensure that the raw data is complying with the acceptance criteria as mentioned in the protocol.
·        Shall report any abnormality and take corrective and preventive action in coordination with respective department head.
Production
HOD/Designee:
·        Shall review the protocol and report.
Operator:
·        Shall ensure and follow the procedure as written in the protocol.
·        Shall operate the equipment during execution.
·        Shall give necessary support to the qualification team.
Engineering
HOD/Designee:
·        Shall review the protocol and report.
Executive/Designee:
·        Shall operate the equipment during execution.
·        Shall provide the technical support for execution.
Microbiology
HOD/Designee:
·        Shall review the protocol and report.
Analyst:
·        Shall analyze the sample, prepare the report and submit to QA.
·        Shall give necessary support to the qualification team.
Note: - In case of qualification performed by External agency/vendor, certificates and raw data shall be prepared by vendor and reviewed by quality assurance department.

4.0     Statement of Purpose

The purpose of this protocol is to provide an outline for the Requalification of the manufacturing and testing areas for the designed cleanliness levels.

5.0     DEFINITIONS

5.1     Air Exchange rate.
Rate of air exchange expressed as number of air changes per unit of time and calculated by dividing the volume of air delivered in the unit of time by the volume of space.
5.2     Average air flow rate
Averaged volume of air per unit of time to determine the air exchange rate in a cleanroom or clean zones.
5.3     Non unidirectional air flow
Air distribution where the supply air entering the clean zone, mixes with   internal air by means of induction.
5.4     Unidirectional air flow
Controlled air flow through the entire cross section of clean zones with steady velocity and approximately parallel steam lines.
5.5     Supply airflow rate
Air volume supplied into an installation from final filters or air ducks in unit of time.
5.6     Total air flow rate
Air volume that passes through section of installation in unit of time.
5.7     Uniformity air flow
Unidirectional air flow pattern in which the point to point reading of velocities are within a defined percentage of average air flow velocity.
5.8     PAO (poly alpha olefin)
A mono-depressed test aerosol of sub-micron particles generated to challenge (evaluate integrity) of HEPA filters.
5.9     Aerosol challenge
Challenging of a filter or an installed filter system by test aerosol.

5.10  Aerosol generator
 System where in aerosol is mixed with particle free dilution air in a known volumetric ratio to reduce concentration.
5.11 Installed filter leakage test
Test performed to confirm that the final filters are properly installed by verifying that there is absence of bypass leakage in the installation  and that filters and the grid system is free of defects and leak.
5.12  Aerosol
 A gaseous suspension of fine (100 µm or smaller in size) solid or liquid particles.
5.13  Aerosol photometer
 Light-scattering mass concentration indicating instrument which uses a forward scattered optical  chamber to make measurements.
5.14  Scanning
Method for disclosing leaks in units, where by the probe inlet of an aerosol photometer is moved in overlapping strokes across the defined filter area.
5.15  Particle
Solid are liquid object which, for purposes of classification of air cleanliness, falls within a cumulative distribution that is based upon a threshold (lower limit) size in the range from 0.5µm to 5.0µm.
5.16  Particle size
 Diameter of a sphere that produces a response, by a given particle – sizing instrument that is equivalent to the response produced by the particle being measured.
5.17  Particle concentrations
 Number of individual particle for unit volume of air.
5.18  Particle size distribution
 Cumulative distribution of particle concentration as a function of particle size.




5.19  Occupancy states
As- Built
Condition where the installation is completed with all services’ connected and functioning but with no production equipment, materials and personnel present.
At- Rest
Condition where the installation is complete with equipment installed and operating but with no personnel present.
Operational

Condition where the installation is complete with equipment installed and operating with personnel present.

6.0     INTRODUCTION TO CLEAN ROOMS & HVAC SYSTEMS

·            The manufacture of sterile products was carried out in clean areas, where entry of air was restricted by airlocks for personnel and/or for equipment and materials.
·            Clean areas are maintained to an appropriate cleanliness standard and supplied with air which has passed through filters of an appropriate efficiency.
·            The various operations of component preparation, product preparation and filling were carried out in separate areas within the clean area.
·            Clean areas for the manufacture of sterile products are classified according to the required characteristics of the environment. Each manufacturing operation has an appropriate environmental cleanliness level in the operational state in order to minimize the risks of particulate or microbial contamination of the product or materials being handled.
·            For the manufacture of sterile medicinal products 4 grades can be distinguished
Grade A: The local zone for high risk operations, e.g. filling zone, stopper, prefilled syringes and vials, making aseptic connections. Normally such conditions are provided by a laminar air flow work station. Laminar air flow systems provide a unidirectional air flow with homogeneous air speed at working position in open clean room applications. The maintenance of laminarity should be demonstrated and validated.
Grade B: For aseptic preparation and filling, this is the background environment for the grade A zone.
Grade C and D: Clean areas for carrying out less critical stages in the manufacture of sterile Products.

·            Classification
Clean rooms and clean air devices are classified as per following
Airborne classification in the European Union guide to good manufacturing practice guideline .
·            Clean room
The Manufacturing area in BBIL has been divided into two areas, as critical (aseptic processing area) and non-critical areas (non-aseptic processing area). The formulation and sterile filtration, filling and sealing are carried out in critical areas Grade-A surrounded by Grade-B. These areas have been provided with separate airlocks for personnel and dynamic pass box for material transfer. All the clean rooms are monitored by BMS System.
Clean areas wall and floors are designed with smooth easily cleanable and free from any crevices or damage all corners are rounded to provide easy and effective cleaning.
Safety devices like fire extinguishers, collapsible safety doors (emergency exit doors) are provided in   the clean room areas. 
Drains points are provided for required areas with water seal and sanitary type.

7.0     EQUIPMENT DESCRIPTION

7.1     AHU
The AHU system is designed to circulate the air in the area after passing it over cooling and heating coils to maintain the required environmental conditions and passing it through the series of filters to maintain desired cleanliness level in the area. The air in-take and out-take of the system is designed to maintain certain degree of pressure gradient in the area as per the requirement
7.2     LAF
The laminar air flow unit is specially designed to ensure and provide particle free, bacteria free, clean air environment needed for working area. This cleaning system also ensures availability of air, free from any kind of particulate matter, screening out everything down to 0.3µm.
7.3     Pass Box
Pass through hatch is provided with electro magnetically inter locked doors to avoid simultaneous opening of both the doors, by controlling the movement of air from one area to the other. Pass through hatch is equipped with UV lamps with hour meter to kill any bacteria if at all present and a florescent lamp is provided for lighting purpose.
7.4     Garment Cubicle
Garment Cubicle is to store sterile garments under grade-A conditions to avoid the contamination and provide a unidirectional airflow.
7.5     Tunnel
Tunnel is used for the depyrogenation of the vials, under grade-A conditions and provides a unidirectional airflow

8.0     QUALIFICATION TEST

8.1     Scheduled Requalification
·         Scheduled qualifications shall be performed as per section no.: 9.0.
8.2     Unscheduled qualification shall be performed through appropriate QMS tool, in case of 
·        Relocation of equipment from one place to another place
·         Installation of a new equipment, Any major modification to the existing equipment
·         Replacement of existing HEPA-Filter or critical component.
·         Frequent surpassing of the alert or action limits of routine environmental monitoring parameters.
8.3     Pre-requisites
Ø  Ensure the identification of the execution team members are trained and record observation in annexure-1.
Ø  Ensure that all instruments used during the qualification activity are duly calibrated and attach the Calibration Certificates to annexure-3.
Ø  Review of preventive maintenance/break down maintenance of the equipment for last 6 months and record in annexure-4.
Ø  Review of incidents and change controls for minor/major modifications of the equipment for last 6 months and record in annexure-5.
Ø  Check the availability of availability SOP’s related to the equipment record observation in annexure-6. Last six months viable monitoring data shall be reviewed and attach the same with Annexure-17.

9.0     QUALIFICATION TEST PLAN AND FREQUENCY

9.1  Air Handling Units
S.No
Test  parameter
Test frequency
Acceptance criteria
1.       
Air velocity and air changes per hour
Every 6 months ±1month
Average velocity and subsequent airflow through supply terminals should meet the design criteria of air change rate as follows.
Grade
Air changes per hour
B
Not less than 60
C
Not less than 40
D
Not less than 20
2.       
HEPA filter integrity test
Every 6 months ±1month
The percentage of leak should be not more than 0.01% for HEPA filters.
3.       
Monitoring of Room pressure
Every 1 year±1month
Pressure differentials should meet the requirement as per the layout drawing Reference No. BB/DW/XXX,XX/006.00
4.       
Temperature and %RH  monitoring
Every 1 year±1month
Temperature and relative humidity should meet the requirement as specified. Temperature should be 23±4°C and relative humidity should be 30-65%RH
5.       
Air flow pattern test
Every 2 years ±1month
Air flow should be from high pressure area to low pressure area when comparing between two adjacent areas. Air flow should be laminar, unidirectional and without any turbulent for all the HEPA in clean room/zone.
6.       
Non-viable particle count  monitoring
(“In-operation” & “At-rest” conditions)
Every 6 months ±1month
“In operation” – 1 run (Grade-A, B & C)
“At rest” – 1 run (Grade-A, B, C & D)
Grade
Maximum permitted number of particles/m3 equal to or above
At rest
In operation
0.5 µm
5.0 µm
0.5 µm
5.0 µm
A
3520
20
3520
20
B
3520
29
352000
2900
C
352000
2900
3520000
29000
D
3520000
29000
Not defined
Not defined
7.       
Sound level test
Every 2 years ±1month
Average sound level should be 55db to 65db at working area.
8.       
Light intensity
test
Every 2 years ±1month
For critical areas (Grade B) 950 – 1000 LUX & Non critical areas (Grade C&D) 450 – 500 LUX.
9.       
Recovery
Every 2 years ±1month
Area should recover to predefined area classification within 15 minutes. (Grade-B & C)
10.   
Viable particle count monitoring.
As per SOP: SAS/012
Refer section No. 10.13.5
Note: After execution of the requalification protocol, Summary matrix shall be recorded in the    
          Annexure-18.

9.2   Laminar air flow units, Pass box, Garment cub1cle and Tunnel:
S.No
Test  Parameter
Test Frequency
Acceptance criteria
1.       
Air velocity
Every 6 months ±1month
Equipment name
Air velocity
LAF
90±20 % FPM.
Pass box
90±20 % FPM.
Sterile garment cubicle
90±20 % FPM.
Tunnel
Drying zone
98±20 % FPM.
Depyrogenation zone
157±20 % FPM.
Cool &stabilization zone
118±20 % FPM.
2.       
HEPA filter integrity test
Every 6 months ±1month
The percentage of leak should be not more than 0.01% for HEPA filters.
3.       
Differential pressure 
Every 1 year±1month
Should be 10-15mm of WC.
For Tunnel drying zone, cooling & stabilization zone 10-15mm of WC and depyrogenation zone 20-25mm of WC).
4.       
Air flow pattern test (“In-operation” and “At-rest”)
Every 2 years ±1month
Air flow should be laminar, unidirectional and without any turbulent for all the HEPA filters of LAF/Pass boxes/ Garment Cubicle/Tunnel.
5.       
Non-viable particle count  monitoring (“In-operation” & “At-rest” conditions)
Every 6 months ±1month
“In operation” – 1 run (Grade-A, B & C)
“At rest” – 1 run (Grade-A, B, C & D)

Grade
Maximum permitted number of particles/m3 equal to or above
At rest
In operation
0.5 µm
5.0 µm
0.5 µm
5.0 µm
A
3520
20
3520
20
B
3520
29
352000
2900
C
352000
2900
3520000
29000
D
3520000
29000
Not defined
Not defined
6.       
Power failure test
Every 2 years ±1month
Should reach desired classification (Grade-A) within 15 min.
7.       
Viable particle count monitoring. ‘In operation’
As per SOP: SAS/012
Refer section No. 10.13.5
Note: After execution of the requalification protocol, Summary matrix shall be recorded in the    
          Annexure-18.

10.0    QUALIFICATION METHODOLOGY
10.1                Measurement of air velocity & calculation of air changes per hour by digital anemometer:
10.1.1 Purpose:
To demonstrate that the air system is balanced and capable of delivering air velocities and providing number of air changes per hour in the respective rooms as per requirement as mentioned in Annexure-2, when calculated as per the respective room volumes.
10.1.2 Principle:
The test is performed to determine the average airflow velocity, volume and uniformity in a clean room, as well as to determine air supply volume flow rate. Air velocity test will be performed and results will be require to determine the air changes per hour for clean room.
10.1.3 Instrument Details:

                     Calibrated digital Anemometer.

10.1.4 Pre-requisite:
Air volumes through supply and return grills and filters should be adjusted as per the design requirement of air change rate and differential pressure. This requirement is only for initial qualification.
10.1.5 Test Procedure:
Ø  Ensure that the supply blower of the AHU is “ON” prior to the start of the observations.
Ø  The velocity shall be measured at approximately 150 mm to 300 mm from the filter face
Ø  When production apparatus and work benches are installed, it is important to confirm occurrence of significant air flow variations, Therefore, the measurement of the uniformity of velocity should not be done at positions close to these obstructions.
Ø  For compliance of air change rate, velocity to be measured at 5 different locations for each Supply grill / diffuser (four corners and center) with the help of calibrated Anemometer as shown in figure-1. (Refer operation of Hot wire anemometer SOP No.: SAS/006).

      Figure-1
 





                          Where V1, V2, V3, V4 & V5 are the measurement locations at supply grill face.

Ø  Calculate the average velocity of the air coming from Supply grill / Terminal filter.

V1 + V2 + V3 + V4 + V5

        5





Average of air velocity at grill (FPM)       =

Ø  Calculate the airflow by multiplying the average velocity with the effective grill area.
Ø  Air flow          =          Average Velocity x Face Area of the Air Inlet Grill / Filter
      =          Ft / Min.  x  Ft 2
      =          Ft 3 / Min. or CFM
Ø  Calculate the total airflow from all the Supply Grill / Terminal Filter in the room and add values to get the total airflow in the room (CFM).
Ø 

ACPH = (Total Room Airflow (CFM) x 60
Room Volume (Cu.ft))




 





Calculate the number of air changes per hour in the room by using the formula :


10.1.6 Observations:
Ø  Record the observations of measurement of air velocity and air changes in Annexure-7.
10.1.7 Acceptance Criteria:
Average velocity and subsequent airflow through supply terminals should meet the design criteria of air change rate as specified in Annexure-2.
10.1.8 Evaluation of Result:
The result complying with the specification range of individual velocity of the supply grill shall achieve the desired airflow of the room and air change rate.

10.2    Measurement of air flow (CFM) & calculation of air changes per hour by Air capture hood.
10.2.1  Purpose
To demonstrate that the system is capable of delivering required number of air changes per hour in the respective rooms as per the requirement  mentioned in Annexure-2.           

10.2.2  Principle
Airflow (CFM) test shall be performed and based on the results obtained number of air changes shall be calculated.
10.2.3  Instrument Details :
Air capture hood (An Air Data Multiplier with Accubalance of flow hood capable of measuring total supply or extract volume from filter housings will be used. The Flow Hoods work on the Wilson grid principal of air measurement and involves the collecting hoods gathering the full volume of air and passing it over the Wilson grid. The pressure readings taken across the grid are fed into the Air Data Multiplier and the instrument produces a direct readout of the volume either in imperial or metric units)

10.2.4  Test Procedure
Ø  Select the correct size hood to fully cover the filter or terminal outlet.
Ø  Select the Volume Programmer (CFM) on the Processor Programmer.
Ø  Read the indicated volume directly from the instrument.
Ø  Ensure that capture hood should cover the HEPA filter area completely and hold the
Hood for a minimum of 10-15 seconds and record the readings in Annexure-7.
10.2.5  Calculations for air changes per hour (ACPH):
One air change occurs in a room when a quantity of air equal to the volume of the room is supplied and/or exhausted. Air change rates are units of ventilation that compare the amount of air moving through a space to the volume of the space. This is the volume of air (usually expressed in cubic feet per minute) exhausted or supplied every hour divided by the room volume (also usually expressed in cubic feet).
Airflow (CFM) is multiplied by 60 minutes to determine the volume of air delivered per hour (in cubic feet).
Room Area (Sq.ft.) = Room Length (ft) x Room Width (ft)
Room Volume (Cu.ft) = Room Area (Sq.ft) x Room Height (ft)

ACPH = (Total Room Airflow (CFM) x 60
              Room Volume (Cu.ft))


 
 



10.2.6  Observations
Record the observation of measurement of air flow and air changes in Annexure-7.
10.2.7  Acceptance Criteria:
Air flow (CFM) through supply terminals and air changes per hour should meet the design criteria as specified in Annexure-2.
Note:  Calculation of air changes per hour shall be carried out either by the calibrated digital anemometer (or) air capture hood method.
10.3                Air velocity measurement test  ( LAF’s , Pass Box, Garment Cubicle and Tunnel):
10.3.1    Purpose:
To demonstrate that the system is balanced and capable of delivering air velocities to provide the desired environment.
10.3.2    Principle:
The test is performed to determine air velocity of the HEPA filters to provide desired      environment.
10.3.3    Instrument Details:

Calibrated digital Anemometer.

10.3.4    Prerequisite:
   Ensure the differential pressure is within the limit as per the design.
10.3.5    Test Procedure:
Ø  Ensure that the supply blower of the LAF/ Pass box/ Garment Cubicle/Tunnel is “ON” prior to the start of the observations.
Ø  The velocity shall be measured at approximately 150 mm to 300 mm from the filter face
Ø  When production apparatus and work benches are installed, it is important to confirm occurrence of significant air flow variations, Therefore, the measurement of the uniformity of velocity should not be done at positions close to these obstructions
Ø  For compliance the velocity to be measured at 5 different locations for HEPA filter (Four Corners and center) with the help of calibrated Anemometer as shown in figure 2. (Refer operation of Hot wire anemometer SOP No.: SAS/006).
      Figure-2
 




                Where V1, V2, V3, V4 & V5 are the measurement locations at supply grill face.

Ø  Calculate the average velocity of the air coming from HEPA filter.

V1 + V2 + V3 + V4 + V5

        5


Average of air velocity at grill =
10.3.6    Observations:
Record the observation of measurement of air velocity and in Annexure-7.
10.3.7    Acceptance criteria:
Parameter
Acceptance criteria
LAF units
90±20 % FPM.
Dynamic Pass Box
Sterile Garment Cubicle
Mobile Laminar Air flow unit
Tunnel
Drying zone
98 ± 20 %FPM
Depyrogenation zone
157± 20%FPM
Cooling zone
118± 20% FPM
10.3.8    Evaluation of result:
The result complying with the acceptance criteria of air velocity.
10.4                HEPA filter integrity test:
10.4.1 Purpose:
To confirm that the filter system is properly installed and to monitor the integrity- leak of the  HEPA filters installed in classified areas / LAF/ Pass Box / Garment Cubicle/ Tunnel.
10.4.2 Principle:
This test is performed to confirm that the HEPA filter is properly installed by verifying the     absence of side leakage in the installation, filter media is free of defects, leaks in the filter frame, gasket seals & leaks in the filter bank frame work. The test is performed by injecting an aerosol challenge upstream of the filters and immediately scanning downstream of the filters and supporting frame.
10.4.3 Instrument details :
Ø  Calibrated Aerosol Photometer & Aerosol Generator.

Ø  PAO Liquid (Poly Alpha Olefin).

10.4.4 Prerequisite:
Filter testing shall be performed only after operational air velocities have been verified and                  adjusted wherever necessary.   
10.4.5 Test procedure:
Ø  Before starting the work take the details of the whole area that to be validate.
Ø  Ensure that required single phase power supply as well as air connection with 20psi (1.5kg) pressure shall be arranged.
Ø  Ensure that the floor and the area as well as equipment is visually cleaned.
Ø  System should be kept ON’ condition,  before starting the measurements.
Ø  Connect the spike guard to photometer before starting it.
Ø  Start the air generate the aerosol particles at 20psi pressure.
Ø  Direct the generator face to the return air point or fresh air intake of the AHU.
Ø  Take a tube and connect one end to the filter face Upstream port and other to the  photometer in upstream mode. Switch on the photometer and set it to zero.
Ø  Put the photometer to Upstream mode and note the reading, the reading should be in between 20µg/liter to 80 µg/liter.
Ø  If it is between the above range than set the value to 100%.wait until the photometer displays 100% upstream concentration.
Ø  Keep the photometer switch on clear mode and enter Zero for Machine to become Zero. Wait until photometer displays ‘0’.
Ø  Now put the switch to Downstream mode and scan the filter by holding the probe approximately 3 cm from the downstream filter face or the frame structure.
Ø  Scan the corners of HEPA filter for checking the installation leakages. Scanning rate(Sr) shall be 15/wp cm/s. (Refer SOP No.: SAS/005).
Ø  If the leakage is less than 5% of the total media, apply the sealant wherever leakages found.
Ø  Repeat the test after the rectification of the Filter.
 










10.4.6 Observations:
                    Record the observations of  HEPA filter integrity test  as per  Annexure-8.
10.4.7 Acceptance Criteria:
The percentage of leak should be not more than 0.01% for HEPA filters.
10.4.8 Evaluation of Result:
Results, complying with the acceptance criteria, shall establish the integrity of the HEPA       filter suitable for system.


10.5                Monitoring of Room Pressure and Differential pressure for equipments:
10.5.1 Purpose:
To demonstrate the capability of the air system to provide room pressure and to ensure the DP of equipments.
10.5.2 Principle:
 This test is performed to confirm that provide room pressure and differential pressure for equipments.
10.5.3 Instrument Details:
  Digital electronic micro manometer (digital display).
10.5.4 Prerequisite:
  All air handling units and the equipment’s shall be in continuous operation.
10.5.5 Test Procedure:
Ø To avoid unexpected changes in air pressure and to establish a baseline, all doors in the
Facility must be closed and no man movement to be allowed during the observations.
Ø Observe the room pressure through digital electronic micro manometer.
Ø Monitor the Room pressure and DP of equipments as per the current SOP’s.
10.5.6 Observations:
Record the observations in Annexure-10. BMS data & raw data shall be attached with the re-qualification report.
10.5.7 Acceptance Criteria:
Pressure differentials should meet the requirement as per the layout drawing Reference No. BB/DW/XXX,/006.00 & differential pressure of equipment’s should be 10-15mm of WC.
10.5.8 Evaluation of Result:
     Results, complying with the acceptance criteria shall indicate that the system is adequate to         provide the  desired room pressure.


10.6                Monitoring of Temperature and %RH:
10.6.1 Purpose:
To demonstrate the ability of the AHU system to provide Temperature and Relative Humidity within the specified range.
10.6.2 Principle:
This test is performed to confirm temperature and relative humidity within the acceptance criteria.
10.6.3 Instrument details :
Digital electronic display unit for Temperature and relative humidity.
10.6.4 Prerequisite:

                    Air conditioning system shall be in continuous operation prior to performing these tests. 

10.6.5 Test procedure:
Observe the temperature and relative humidity through respective display unit wherever installed as per the current SOP.  
10.6.6 Observations:
Attach the BMS data to the report. Record the observations in Annexure-11 (if necessary).
10.6.7 Acceptance criteria:
Temperature and relative humidity should meet the requirement as specified. Temperature should be 23±4°C and relative humidity should be 30-65%RH.  
10.6.8 Evaluation of result :
Results, complying with the acceptance criteria shall indicate that the system is adequate to provide the desired environmental condition of temperature and relative humidity. 
       Note:  If necessary, Data loggers shall be placed in all classified rooms for observation of temperature & %RH. The data loggers shall be placed near every return air grill of each room as it is considered as a worst case location.


10.7                Air Flow Pattern Test:
10.7.1    Purpose:
To describe a procedure for carrying out air flow pattern test by using glycol/dry ice in hot water/ water fogger during ‘In-operation’ and ‘At-rest’ conditions.
10.7.2    Principle:
The purpose of air flow pattern test is to confirm the airflow direction, uniform flow, and to conform the design and performance specifications and, if required, spatial and temporal characteristics of airflow in the installation.
10.7.3    Prerequisite:

All AHU’s, LAF‘s/ Pass Box/Garment Cubicle/Tunnel shall be in continuous operation.

10.7.4    Test Procedure (Dry ice fogger operation method):
Place the dry ice fogger on a flat, level bench, table or rolling cart.
Ø Fill with WFI up to ¾ of tank level and ensure that the hose pipe was connected.
Ø Remove the hose cap and add dry ice manually.
Ø Connect optional fog curtain tube to hose to create a fog wall to visualize air flow.
Ø Refill dry ice to continue fogging or drain WFI by opening the drain plug and refill fresh WFI.
Ø Expose the smoke near the supply grill / diffusers / filter. And move the fogger gradually from supply grill / diffusers / filter to return grill / riser / diffuser / fitters.
Ø Quantity of smoke should be sufficient to demonstrate the flow. It should not be denser and should not be very less. The airflow pattern should ensure that entire controlled and specified areas are swept efficiently by the airflow, in order to ensure that both contamination control and environmental control are achieved.
10.7.5    Observations:
Observe the air flow pattern as per the procedure mentioned above and record the study    through camera. Record the details as per the Annexure-12. Secure necessary videotapes / CD and Photographs.
10.7.6    Acceptance Criteria:
Ø  Air flow should be from high pressure area to low pressure area when comparing between two adjacent areas
Ø  Air flow should be laminar, unidirectional and without any turbulent for all the HEPA in clean  room/zone
Ø  Air flow should be laminar, unidirectional and without any turbulent for all the HEPA filters of LAF/Pass boxes/ Garment Cubicle/Tunnel.
10.7.7    Evaluation of Result:
Compliance to the acceptance criteria shall be established.


10.8                Non-Viable Particle Count Test:
10.8.1    Purpose:
To describe a procedure for carrying out Non-Viable particle count test to classify the clean room  installation.
10.8.2    Principle:
This test method specifies the measurement of air born particle concentrations with size distributions having threshold size between 0.5µm and 5.0µm. Measurement can be made in any of three defined occupancy states as-built, at-rest and operational. The measurement is made to certify the cleanliness classification.
10.8.3    Instrument Used:
Particle counts are measured with a Discrete Laser Particle Counter with Iso-kinetic probe, which is calibrated once in a year.
10.8.4    Prerequisite:
Tests covered in preceding sections for Air velocity measurement and Air change rate calculation, HEPA filter integrity test and differential pressure control test should be completed and results should comply with respective acceptance criteria.

10.8.5    Establishment of number of sampling locations:
Refer the below table to calculate the minimum number of sampling point locations:
ESTABLISHMENT OF NUMBER OF SAMPLING LOCATIONS
Area of Cleanroom (m2) less than or equal to
Minimum number of sampling locations to be tested {NL}
Area of Cleanroom (m2) less than or equal to
Minimum number of sampling locations to be tested {NL}
2
1
76
15
4
2
104
16
6
3
108
17
8
4
116
18
10
5
148
19
24
6
156
20
28
7
192
21
32
8
232
22
36
9
276
23
52
10
352
24
56
11
436
25
64
12
636
26
68
13
1000
27
72
14
>1000
See below Formula
Note: 1)  If the considered area falls between two values in the table, the greater of the two should be selected.
          2)  In the case of unidirectional airflow, the area may be considered as the cross section of the moving air perpendicular to the direction of the airflow. In all other cases the area may be considered as the horizontal plan area of the cleanroom or clean zone.
When the area of the cleanroom or clean zone is greater than 1000 m2, apply the below mentioned formula to determine the minimum number of sampling locations required.
Where, ‘NL is the minimum number of sampling locations to be evaluated, rounded up to the next whole number, ‘A’ is the area of the clean room or clean zone in m2. Ensure that the sampling locations are evenly distributed to cover the entire area of the clean room and positioned the probe at the working level.
10.8.6    Establishment of sampling volume:
At each sampling location, sample a sufficient volume of air that a minimum of 20 particles would be detected if the particle concentration for the largest considered particles size were at the class limit for the designed Grade .
The single sample volume Vs per locations is:
VS= 20/Cnm X 1000
Where,
Vs is the minimum single sample volume per locations in liters
Cnm is the limit (number of particle per cubic meter) for the largest considered particle size specified for the relevant class.
20 is the defined number of particle that could be count if the particle concentration were at the class limit.
Sampling volume:
S. No
Grade
Sample  volume/location
At rest
In operation
1
A
1000 liters
1000liters
2
B
690 liters
7 liters
3
C
7 liters
2liters
4
D
2liters
Not Defined







10.8.7    Sampling locations:
Ensure that the sampling locations are evenly distributed throughout the area of the clean room and positioned at a working level.
10.8.8    Method:
Ø  Particulate counting shall be carried out at predefined locations as per the layout drawing Reference No. DW/XXX,/041.03 & DW/XXX,/008.03
Ø  Before starting the work take the details of the whole area that to be validate
Ø  Clean all instruments with 70% IPA before entering in clean area
Ø  Ensure that the floor area as well as equipment is visually cleaned.
Ø  System should be kept ON, 2 hour before starting the measurements.
Ø  The particle counter is kept on a SS trolley and all setting shall be done.
Ø  Connect the spike guard to particle counter before starting counter.
Ø  Set the particle counter as per given details of rooms/equipments.
Ø  The sampling shall be positioned vertically upward.
Ø  Switch ON airborne particle counter.
Ø  Set the particle counter for zero purging before starting the measurements.
Ø  Place the probe at working level height.
Ø  Start taking samples at different locations as per details and take print of readings.
Ø  The test is used for measurement of airborne particle concentration with size distribution  having a threshold size between 0.5 µ to 5 µ to certify the cleanliness of the classified room.
Ø  The sampling locations shall be calculated and are evenly distributed throughout the area of the clean room and are monitored at the height of the working area.
Ø  After completion of monitoring take the thermal print from the counter and stick the thermal print on Annexure-13A and the same annexure should be photocopied or after completion of monitoring download the data through USB pen drive, and print the same and attach with the Annexure-13A. (Refer operation of Off-line NVPC SOP No.: SAS/003).
10.8.9       Observations:
Ø  The cumulative counts of the particle shall be counted  for  m3 as per EU guidelines.
10.8.10   Acceptance criteria:
The system shall meet the acceptance criteria for an air borne particulate cleanliness as per section no. 10.8.5.
10.8.11   Evaluation of result :
Results, complying with the acceptance criteria shall indicate that the system is adequate to provide the desired cleanliness class in the area.
S.No
Qualification Type
Test condition
Number runs
Test shall be performed in

1.
Scheduled Requalification
At-Rest
1 run
Grade-A, B, C &  Grade-D
In-Operation
1 run
Grade-A, Grade-B &  Grade-C
10.8.12   Number of runs for Non-viable particle count:
10.9                Sound Level Test:
10.9.1    Purpose:
To verify that the sound level is in limit in the clean room area
10.9.2    Principle:
This test is performed to confirm that sound level is within the acceptance criteria in the            clean room area
10.9.3    Instrument Details:
Duly Calibrated Sound Level Meter
10.9.4    Prerequisite:
Tests covered in preceding sections for Air Velocity Measurement and Air Change Rate   calculation, HEPA filter integrity test and room pressure control test should be completed & results should comply with respective acceptance criteria
10.9.5    Test Procedure:
Take the reading at working level in 5 different locations in the room and take the average of the sound in the unit of Decibel (db)
10.9.6    Observations:
Record the sound level test observations in Annexure-14.
10.9.7    Acceptance Criteria:
Average sound level should be 55-65 db at working area.
10.9.8    Evaluation of Result:
Results, complying with the acceptance criteria shall indicate that the sound level in the clean room is in limits.
10.10            Light Level Test:
10.10.1Purpose:
            To verify that the Light level is in limit in the clean room area
10.10.2Principle:
This test is performed to confirm that light  levels are within the acceptance criteria in the      clean room area.
10.10.3Instrument Details:
Duly calibrated light level meter.
10.10.4Prerequisite:
 During this test the all equipment’s should be ‘ON’ / operation mode.
10.10.5Test Method: 
Take the reading at working level at 5 different locations in the room and take the average of the light level in the  unit  of Lux  
10.10.6Observations:
                  Record the light level test observations in Annexure-15.
10.10.7Acceptance Criteria:
                 The clean room or clean zone shall meet the acceptance criteria for light level as mentioned below
S.No
Cleanliness Class
Lighting Level Limit (lux)
1
Critical Areas (Grade B)
950 to 1000 lux
2
Non Critical Areas (Grade C &  Grade D)
450 to 500 lux
10.10.8Evaluation of Results:
Results, complying with the acceptance criteria shall indicate that the light level in the clean room is in limits.
10.11      Recovery Test:
10.11.1   Purpose:
                    To describe a procedure for carrying out recovery test for critical areas like Grade-B & C.
10.11.2   Principle:
This test method species whether the installation is capable of returning to it’s specified      area classification within a finite time, after being exposed briefly to a source of airborne particulate challenge. Recovery test shall be performed only in Grade-B & Grade-C.
10.11.3   Instrument Details:
Particle counts are measured with a discrete laser particle counter with ISO-kinetic probe,    which is calibrated once in a year.
10.11.4   Prerequisite:
Tests covered in preceding sections for Air velocity measurement and air change rate calculation, HEPA filter integrity test differential pressure control and non-viable particle count  Test should be completed and results should comply with respective acceptance criteria 
10.11.5   Test Method:
Ø  Evaluation by 100:1 recovery time.
Ø  This test performed only critical areas like Grade B & C (which are surrounded by grade B) areas (Aseptic Area).
Ø  Operate all the AHU’s as per the standard operating procedure (EMD/001).
Ø  Before start the observation, verify the Instrument/s calibration reports for the adequacy and validity. Attach the calibration certificate.
Ø  Set up the particle counter in accordance with the manufacturer's instructions and the apparatus calibration certificate.
Ø  Place the DPC probe at the testing point.
Ø  The DPC probe should not be placed directly under the air outlet.
Ø  Adjust the single sample volume to the same value used for determining the cleanliness class. The delay time of the counter from starting each count to the output recording should be adjusted to not more than 10s.
Ø  The particle size used in this test should be less than 1 µm. It is recommended that the size channel used by the DPC corresponds to that of the maximum number concentration of the aerosol.
Ø  Run the DPC for initial count 1 min when air-handling units are in ON condition.
Ø  Switch OFF the AHU and not down the time.
Ø  Raise the initial particle concentration to 100 or more times the target cleanliness level with an aerosol
Ø  Run the Particle counter with 1 min interval with cycle mode. Note the time when the particle concentration reaches the 100 x target concentration threshold ( t100n )
Ø  ON the AHU and Note down the time.
Ø  Run the Particle counter with 1 min interval with cycle mode up to reach the initial count note. (Refer operation of Off-line NVPC SOP No.: SAS/003).
Ø  Note the time when the particle concentration reaches the target cleanliness level (tn)
Ø  The  100 : 1 recovery time is represented by   t0.01= (tn - t100n)
10.11.6   Observations:
Record the observations in the Annexure-16. Raw data shall be attached with the report either in pdf format or raw data shall be pasted directly.
10.11.7   Acceptance Criteria:
Area should recover to predefined area classification within 15 minutes.
10.11.8   Evaluation of Results:
Results, complying with the acceptance criteria shall indicate that the Recovery Time within limits.
10.12      Power failure test:
10.12.1   Purpose:
To describe a procedure for carrying out Power failure test for the Equipment like Pass box, LAF, mobile LAF and Sterile garment cubicle.
10.12.2   Principle:
This test method species whether the installation is capable of returning to its specified Cleanliness class within a finite time, after the power failure.
10.12.3   Instrument Details:
Particle counts are measured with a discrete laser particle counter with ISO-kinetic probe,    which is calibrated once in a year.
10.12.4   Prerequisite:
Tests covered in preceding sections for Air velocity measurement and air change rate calculation, HEPA filter integrity test differential pressure control and non-viable particle count  tests should be completed and results should comply with respective acceptance criteria 
10.12.5   Test Method:
Ø  This test is performed to know its capability of recovery time i.e. maintaining of desired grade specifications after power failure.
Ø  Operate all the equipment as per the standard operating procedure.
Ø  Before the test, verify the Instrument/s calibration reports for the adequacy and validity. Attach the calibration certificate.
Ø  Set up the particle counter in accordance with the manufacturer's instructions and the apparatus calibration certificate.
Ø  Place the DPC probe at the testing point.
Ø  The DPC probe should not be placed directly under the air outlet.
Ø  Adjust the single sample volume to the same value used for determining the cleanliness class. The delay time of the counter from starting each count to the output recording should be adjusted to not more than 10sec.
Ø  The particle size used in this test should be less than 1 µm. It is recommended that the size channel used by the DPC corresponds to that of the maximum number concentration of the aerosol.
Ø  Run the DPC for initial count minimum 1 min when LAF is in ON condition.
Ø  Switch OFF the LAF (Including UPS) and not down the time in annexure-16.
Ø  Run the Particle counter with 1 min interval with cycle mode, then power shall be ON.
(Note: The particle counter should be ON with continuous cycle mode @ before and after the Power failure). Refer SOP No.: PGD/026.
10.12.6   Observations:
Ø  Record the observations and results in the Annexure-16.
10.12.7   Acceptance Criteria:
Ø  Should reach desired classification within 15 min.
10.13      Viable particle count test:      
10.13.1   Purpose:
              To determine the air borne microbial contamination level in clean area  
10.13.2   Principle:
This test method is to determine the air borne microbial contamination level in clean area is within   the   acceptance criteria
10.13.3   Test methodology: 
Viable particle count monitoring shall  be performed as per the SOP No. xxx.
10.13.4   Observations:
        All the observations of passive & active air sampling details are recorded by the QC Microbiology department as per SOP No.: xxx. And the same was attached with Annexure-17.

10.13.5   Acceptance Criteria:
The following limits for passive & active air sampling shall be followed during monitoring of viable count. (As per SOP No.: SAS/012).
     
 Viable Particulate Count Test          
Viable Particulate Count results should be within the acceptance criteria as per SOP No. SAS/012.
Passive Air Sampling
Active Air Sampling
Grade
Alert limit
Action limit
Alert limit
Action limit
A
<1
1
<1
1
B
3
5
6
10
C
35
50
75
100
D
85
100
95
200
10.13.6   Evaluation of Results:
    Results, complying with the acceptance criteria shall indicate that the viable particle count            in limits in clean area. The SOP No.: xxxxx shall be followed for monitoring of viable count during the qualification

11.0    ACTION TO BE TAKEN IN CASE OF QUALIFICATION FAILURE
11.1    Air Velocity Test:
Action to be taken in case air change rate is less than the design limit in non-unidirectional air flow zone.
Ø   During requalification:
Immediate Action:
Ensure that all damper position is in preset marked location. If change in air change rate is due to reduction in velocity across the HEPA filter, replace the HEPA filter with new one.


Preventive Action:
Check for any leakage in the duct line, which can increase the particulate load in the inlet air. Check the preventive maintenance record of last six-month, whether any leakage in the duct line is observed. Check that in the last six month any time AHU was shut down for long period and air change rate was verified during the startup after shut down. In case of shifting of damper position, investigate for the reason for shifting. Check the preventive maintenance record, whether damper position is verified.
11.2    HEPA Filter Integrity Test:
During requalification:
Different types of leakages and their corrective actions to be taken are mentioned in the following table.
 Description of leakage
Corrective action to be taken
Leak from the gasket and the filter edge
Tightening the filter frame from all sides. If the leak continues to occur, observe the condition of the gasket. If the gasket is damaged, replace the gasket and perform the test again. For Gel filled filters, the filter must be removed and checked for proper filling of the gel in groove.
Leak between the filter and  frame
Apply silicone sealant to the leak. (Replace the HEPA filter as per ISO 14644-3).
Leak from the filter medium
Apply silicone sealant to the leak. (Replace the HEPA filter as per ISO 14644-3).
      Replacement of HEPA filter:
After replacement with new HEPA filter, Tests like Air velocity, filter integrity, Non-viable particle count tests shall be performed.
12.0    DEVIATIONS, DISCRIPENCY & CORRECTIVE ACTION REPORT:
If any deviations observed during Re-qualification with respect to protocol the deviation shall be recorded in Annexure-19. If any discrepancy observed during performance qualification with respect execution, the discrepancy and corrective action shall be handled through appropriate QMS tool and recorded in Annexure-20.
13.0    CONCLUSION & SUMMARY REPORT:
After completion of qualification, qualification summary report shall be prepared as per the protocol and with the details of results of the qualification study. A conclusion shall be drawn based on the results of qualification study of the equipment.
14.0    ANNEXURES:
Annexure No.
Details of the Annexure
Annexure-1
Identification of execution team and training record
Annexure-2
Equipment details
Annexure-3
Verification of calibration  details
Annexure-4
Preventive maintenance details
Annexure-5
Review of incidents and change controls
Annexure-6
Verification of availability of SOP’s
Annexure-7
Measurement of air velocity and air changes per hour record
Annexure-8
Measurement of air velocity (LAF, pass box, garment cubicle and tunnel)
Annexure-9
HEPA filters integrity testing record
Annexure-10
Differential pressure monitoring record
Annexure-11
Temperature & %RH mapping record
Annexure-12
Air flow pattern test details
Annexure-13
Non-viable particle count raw data record and rationale for the NVPC locations
Annexure-14
Sound level test record
Annexure-15
Light level test record
Annexure-16
Recovery/ Power failure test record
Annexure-17
Viable monitoring test results
Annexure-18
Summary matrix
Annexure-19
Deviation record
Annexure-20
Discrepancy and corrective action report

15.0    PROTOCOL HISTORY
Revision No.
Change Control No
Revision Description
03

·   Implementation of revised ISO-14644-1, 2nd edition (2015)
·   95% UCL calculation removed
·   NVPC monitoring locations for room wise has been revised.
·   NVPC locations rationale has been incorporated.
·   Maximum number of persons allowed for grade B& C during NVPC activity (in-operation condition) has been incorporated.
·   Pass box classification changed.
16.0    ABBREVIATION:
Abbreviation
Extended Form
AHU
Air Handling Unit
CRQ
Cleaning room qualification
CFM
Cubic Feet per Minute
LAF
Laminar air flow
PBX
Pass box
SGC
Sterile garment cubicle
HEPA
High Efficiency Particulate Air
MOC
Material Of Construction
PAO
Poly Alpha Olefin
db
Decibels (Unit of Sound)
FPM
Feet Per Minute
AHU
Air Handling Unit
LAF
Laminar Air Flow
MOC
Material Of Construction
QA
Quality Assurance
%RH
Relative Humidity
RPM
Revolutions Per Minute

WC
Water column
SOP
Standard operating procedure
BMS
Building monitoring system
WFI
Water for injection
CD
Compact disc
UCL
Upper concentration limit
NMT
Not more than
NLT
Not less than
HVAC
Heating Ventilation and Air Conditioning
ACPH
Air changes per hour
DP
Differential pressure
SS
Stain less steel
NVPC
Non-viable particle count
QC
Quality control
QMS
Quality management system
SAS
Sterility assurance services






17.0    REFERENCES
·         ISO 14644-1, 2nd edition (2015)
·         EUGMP Annexure-1
·         WHO TRS 961 Annexure-5
·         Requalification Protocol no. RQP/XXX/CRQ/001/01






















18.0    PROTOCOL APPROVAL
The signatures listed below indicate approval of the Re-qualification protocol and certify that it may be executed.

PREPARED BY
Name
Department
Designation
Signature &Date





CHECKED BY
Name
Department
Designation
Signature & Date

















APPROVED BY
Name
Department
Designation
Signature & Date






No comments:

Post a Comment

Autoclave PQ protocol